MEWOI
Home
/
Earth Resistance & Grounding Test

MEWOI3000C+ Explosion-Proof Clamp Earth Resistance Tester

MEWOI3000C+

Intrinsically safe clamp-on earth resistance tester certified Ex ia IIB T3 Ga for use in explosive gas atmospheres: 0.01–1200Ω loop resistance without disconnecting the earth.

Earth Resistance & Grounding Test
Clamp-On Earth Resistance Tester
Handheld Clamp Meter
GB 3836 (Ex ia IIB T3 Ga)
Enquire About This Product
MEWOI3000C+ explosion-proof clamp earth resistance tester

Overview

Earthing at fuel terminals, refineries, gas plants and mines has to be checked where a standard instrument cannot be taken. The MEWOI3000C+ is an intrinsically safe version of MEWOI's clamp-on earth tester, certified to GB 3836 with the marking Ex ia IIB T3 Ga (certificate CE18.2380), so it can be used in the corresponding explosive gas atmospheres.

Like other clamp-on testers it measures earth and loop resistance by clamping around the earth conductor, with no auxiliary stakes and no need to disconnect the electrode from a multi-earthed system. Readings from 0.010Ω to 1200Ω are taken in 0.5 seconds; an audible and visual alarm flags values above a set threshold (1–199Ω), and a noise indicator warns when interference may affect the result. It runs for around 30 hours on four AA alkaline cells and stores 99 readings.

Key Specifications

SpecificationMEWOI3000C+
Resistance range0.010Ω–1200Ω
Accuracy±(1%rdg + 0.01Ω) at 0.010–0.99Ω; ±(1%rdg + 0.1Ω) to 49.9Ω; wider above
Resolution0.001Ω
Explosion protectionEx ia IIB T3 Ga, certificate CE18.2380 (GB 3836)
Jaw size65 × 32mm
Measurement time0.5s
AlarmAudible/visual, threshold 1–199Ω; interference (NOISE) indicator
Memory / interface99 readings; RS232 optional
Power4 × LR6 (AA) alkaline, ≤50mA, approx. 30h continuous
Operating environment-20 to 55°C, 20–80% RH
Size / weight285 × 85 × 56mm / 1.1kg

Features

Applications

Earthing checks at fuel depots, refineries, gas processing plants and chemical sites; hazardous-area electrical maintenance; lightning protection earthing in classified zones.