MEWOI stake-method earth resistance testers from the basic 3-terminal MEWOI4105A to 4-wire soil resistivity, dual-clamp and untie-free tower testers measuring up to 30kΩ and 9000kΩm.
Enquire About This Product
Stake-method earth testers inject current between the electrode under test and auxiliary spikes driven into the ground, and measure the voltage drop to calculate resistance. Unlike a clamp-on tester they work on single, isolated electrodes and new installations, and the 4-wire (Wenner) arrangement measures soil resistivity for designing an earthing system before it is installed.
The range builds up in capability. The MEWOI4105A is a simple 3-terminal tester with 20/200/2000Ω ranges. The MEWOI4000 and 4000D add 2- and 3-wire testing to 2000Ω with earth voltage and 400-set memory. The MEWOI4000C and 4200D add 4-wire soil resistivity and extend the range to 30kΩ. The MEWOI4200 and 4300D combine all of these with dual-clamp (stakeless) measurement, AC leakage current to 600A and 2000-set memory. The MEWOI4250 is built for transmission towers and substations, measuring a tower's footing resistance with four clamps without disconnecting the down-leads.
| Model | Earth resistance | Soil resistivity | Methods / extras | Memory |
|---|---|---|---|---|
| MEWOI4105A | 20 / 200 / 2000Ω, ±(2%+0.1Ω) | — | 3-terminal; earth voltage to 200V | — |
| MEWOI4000 | 0.01Ω–2000Ω | — | 2/3-wire; earth voltage 0–600V; RS232 | 400 sets |
| MEWOI4000D | 0.01Ω–2000Ω | — | 2/3-wire; earth voltage 0–600V; RS232 | 400 sets |
| MEWOI4000C | 0.01Ω–30kΩ | 0.01Ωm–9000kΩm | 2/3/4-wire; earth voltage 0–600V | 300 sets |
| MEWOI4200D | 0.01Ω–30kΩ | 0.01Ωm–9000kΩm | 2/3/4-wire; earth voltage 0–600V | 300 sets |
| MEWOI4200 | 0.01Ω–30kΩ; dual clamp 0.01–100Ω | 0.01Ωm–9000kΩm | 2/3/4-wire, selective and dual-clamp; AC leakage 0–600A; earth voltage 0–100V | 2000 sets |
| MEWOI4300D | 0.01Ω–30kΩ; dual clamp 0.01–100Ω | 0.01Ωm–9000kΩm | 2/3/4-wire, selective and dual-clamp; AC leakage 0–600A; earth voltage 0–100V | 2000 sets |
| MEWOI4250 | 0.10Ω–20kΩ; 4-clamp 0.10–200Ω | to 9000kΩm | Untie-free tower method; AC current 1mA–500A; earth voltage 0–200V | 100 sets |
Earthing system design and commissioning; soil resistivity surveys; substation and transmission tower footing resistance; lightning protection earth testing; telecom and industrial site earthing.