Turns ratio testing — covered in our companion article — verifies that a transformer's windings have the correct number of turns relative to each other. DC winding resistance testing checks something related but genuinely different: whether the physical copper path through each winding has the low, consistent resistance it should.


What Winding Resistance Testing Catches

A DC winding resistance test applies a stable DC current through a winding and measures the resulting voltage drop, calculating resistance directly. This is specifically sensitive to fault types that don't necessarily affect turns ratio:

Loose or degraded connections. A connection that's loosened over time or corroded shows up as elevated resistance, even though the winding itself is completely intact.

Broken strands within a winding. A partially broken strand reduces effective conductor cross-section and raises resistance without creating a complete open circuit.

Tap changer contact wear or misalignment. Worn or pitted contacts show up as elevated resistance at the affected tap positions.

Shorted turns. A winding with shorted turns also typically shows reduced resistance, providing a useful cross-check with turns ratio testing.


Why a Standard Ohmmeter Doesn't Work

Transformer winding resistance values are typically very low — often well under an ohm. At these levels, test lead and contact resistance becomes significant, which is why winding resistance testing uses dedicated micro-ohmmeters (DLROs) employing four-wire (Kelvin) measurement, isolating the actual winding resistance from the test setup's own lead resistance.


Why the Test Takes Time

Transformer windings are highly inductive. When DC current is first applied, it doesn't reach steady-state instantly — an accurate reading can only be taken once current has stabilised, which can take seconds to minutes per measurement for large windings. Higher test current drives the winding to saturation faster, shortening test duration.


Temperature Correction

Winding resistance varies with temperature, and meaningful comparison between tests requires correcting measured resistance to a common reference temperature, using the winding's actual temperature measured directly via a probe.


A Complete Transformer Electrical Test Program

TestWhat it verifiesWhat it can miss
Turns ratio (TTR)Correct turns count, shorted turns, tap changer ratioConnection resistance problems that don't affect ratio
DC winding resistancePhysical conductor and connection integrityTurns count errors that don't significantly affect resistance
Insulation resistance / PI / DARInsulation condition between windings and to groundConductor and connection integrity
Dielectric withstand (hipot)Insulation's ability to withstand overvoltage stressNormal-operation conductor issues