LISUN LS-RCT automatic RCD testers for Type AC, A, B and F RCCBs, RCBOs and IC-CPDs: AC, pulsating DC, smooth DC and HF waveforms, 2mA to 10A, 1ms timing.
Enquire About This ProductResidual current devices are classified by the residual current waveforms they detect: Type AC for sinusoidal current, Type A also for pulsating DC, Type F also for composite frequencies, and Type B also for smooth DC. EV chargers, inverters and variable speed drives make Type A, F and B devices increasingly common, and each must be tested with the waveforms its type covers.
The LS-RCT systems test RCD operating characteristics automatically under microcontroller control. The LS-RCT-ABCF7A covers Types AC, A, B and F, with sinusoidal, pulsating DC at 0°, 90° and 135°, DC-superimposed, two- and three-phase rectified, smooth DC, high-frequency (100Hz to 1kHz) and composite waveforms up to 7A. The LS-RCT-AC10A covers Types AC and A up to 10A. Both supply the device at fixed three-phase test voltages, time trips with 1ms resolution, and alarm on non-compliant results, suiting both production line testing and type testing.
| Specification | LS-RCT-ABCF7A | LS-RCT-AC10A |
|---|---|---|
| Device types | AC, A, B and F | AC and A |
| Supply | AC 380V ±10%, 50/60Hz | |
| Output voltage | Three-phase, phase voltages 50, 110, 187, 220, 242V | |
| Max output frequency | 1kHz | |
| Voltage display | 0.1V resolution, class 1.0 | 0.1V resolution, class 0.5 |
| AC residual current | 2mA~7A, 0.1mA resolution | 2mA~10A, 0.1mA resolution |
| Current accuracy | Type AC class 0.3; Type A class 2.0 | Type AC class 0.5; Type A class 2 |
| Type A pulsating DC | 0°: 5mA~6A; 90°: 5mA~4A; 135°: 5mA~2.5A | 0°: 5~6000mA; 90°: 5~4000mA; 135°: 5~2000mA |
| Type A polarity | Positive, negative, positive + 6mA DC, negative + 6mA DC | |
| Waveforms | AC sine; pulsating DC; DC superimposed; 2- and 3-phase rectified; smooth DC; HF sine; composite | AC sine; pulsating DC 0°, 90°, 135° |
| HF sine | 100Hz~1kHz in 50Hz steps, class 0.3 | – |
| Smooth DC / composite | Class 0.5 | – |
| Timing | 5ms accuracy, 1ms resolution | |
| Insulation resistance | ≥10MΩ | |
| Alarm | Audible and visual on non-compliance | |
The LS-RCT-ABCF7A if you make or test Type B or F devices, including EV charging protection; the LS-RCT-AC10A for Type AC and A devices up to 10A.