LISUN
Home
/
High Voltage Test Equipment

SUG255 Impulse Voltage Generator (1.2/50μs) – LISUN

SUG255LX / SUG255MX / SUG255PX / SUG255PX-20KV / SUG255PX-25KV / SUG255PX-30KV

LISUN SUG255 impulse voltage generators: 1.2/50μs impulse up to 12kV, 20kV, 25kV or 30kV for insulation tests to IEC 60255-5 and IEC 60060-1.

High Voltage Test Equipment
Impulse Withstand Voltage Tester
Bench-top Instrument
IEC 60255-5:2000; IEC 60060-1:2010; IEC 60065:2005; IS 13252-1:2008; GB/T 14598.3-2006; GB/T 3048.8-2007; GB/T 17215.301-2007; GB/T 17215.322-2008
Enquire About This Product
LISUN SUG255 Impulse Voltage Generator (1.2/50μs)

Overview

An impulse voltage test checks that a product's insulation can survive the brief high-voltage spikes it will meet in service, such as lightning-induced overvoltage on the grid or switching overvoltage. The SUG255 series applies the standard 1.2/50μs high-voltage impulse to find insulation weak points before they cause leakage, short circuits or burnt-out equipment.

Output is up to 12kV on the LX, MX and PX models, and up to 20kV, 25kV or 30kV on the high-voltage PX versions, with positive or negative polarity, manual or automatic operation and up to 9,999 impulses. A large Android touch screen in English and Chinese runs the tests.

It is used for insulation testing of relays, electricity meters, LED lighting, medical devices, EV chargers, small motors, low-voltage switchgear and household appliances.

Key Specifications

SpecificationSUG255LXSUG255MXSUG255PXSUG255PX-20KVSUG255PX-25KVSUG255PX-30KV
Output voltage0~12kV0~20kV0~25kV0~30kV
Generator impedance12Ω and 500Ω38Ω and 500Ω2Ω and 500Ω
Waveform1.2/50μs
PolarityPositive and negative
OperationManual and automatic
Impulse count1~9,999
Interval3~9,999s

Features

Applications

Frequently asked questions

Is this the same as a surge generator?

No. An impulse voltage generator tests insulation strength with a 1.2/50μs voltage impulse. A surge generator (IEC 61000-4-5) tests immunity with a combination wave that also delivers 8/20μs current into the circuit.

Which impedance do I need?

It is set by your standard: IEC 60255-5 for relays uses 500Ω, while other product standards call for lower impedances. Choose the model whose impedance matches.